Mounting and Wiring
Immersion type probes are designed to measure the temperature inside pipes carrying liquid or steam. They are installed in a brass (for noncorrosive liquids) or 304 stainless-steel (for corrosive liquids) thermowell. Mount the thermowell horizontally or with the open end facing down, to allow any condensation to drain. Position the thermowell to prevent contact with the inside of the pipe.
1. Install the pipe fittings required, by local code, for a thermowell into the dry/drained pipe. If the system is pressured, use a hot tap.
2. Install the thermowell. (See the Accessories section.)
3. Fill the well with thermal compound to ensure complete conductivity from well to probe. Note: The probe can slide within its collar on the case as it is inserted into the thermowell.
4. Remove the screws holding the cover to the case and remove the cover.
5. Insert the probe into the well and tighten the threaded connection on the case.
6. From inside the case, push the probe as far as it will go into the well.
7. Feed the thermistor wire leads through the conduit or hole opening. Note: The two-wire sensor is polarity insensitive.
8. Connect the thermistor wires to the cable with butt-splices or soldering (wire nuts are not recommended).
9. Reinstall the cover and screws
Accessories
The following thermowells are available for the STE–1421 and STE–1422:
HMO–4533 4" brass well HMO–4534 4" 304 stainless-steel well HMO–4543 6" brass well HMO–4544 6" 304 stainless-steel well Note: NPT Thread Size = 1/2"
Controller Configuration
Note: Controller configuration instructions are given for both WinControl and BACstage. See the relevant software section.
WinControl
1. In the WinControl software main menu, select Control > Inputs.
2. Click Edit.
3. Type in a name in the Description field (up to 20 characters) and/or Label field (up to 8 characters). Note: No two labels or descriptions in a controller can be identical.
4. Click Units (which opens the Configure Inputs screen).
5. Select Type: Analog if it is not the default.
6. Select Deg F (or C) KMC10K Type III.
7. Optionally, adjust the Calibration value.
8. Optionally, change Format from 0 to the desired number of temperature decimal places.
9. Optionally, change the Average to the desired number of thermistor readings averaged before displaying the result.
10. Click OK.
11. Click End Edit.
12. Click OK
BACstage
1. In the BACstage software main menu, select Objects > Inputs.
2. Click Edit.
3. Type in a name in the Description field (up to 32 characters) and/or Label field (up to 16 characters). Note: No two labels or descriptions in a controller can be identical.
4. Select Object Type: Analog if it is not the default.
5. Select Device Type: KMC10K Type III.
6. Select Units: °F or °C.
7. Click End Edit.
8. Click Yes for “Send Update Notification Now?”
9. In the BACstage software main menu, select Device > Device Tables > KMC10K Type III Table.
10. Click Edit.
11. Click Defaults (values will fill in).
12. Click End Edit.
13. Click Yes for “Send Update Notification Now?”
14. Click OK
Specifications Standard
Lengths 4" (STE–1421), 6" (STE–1422)
Sensor Type III, 10K ohm @ 77° F (25° C)
Accuracy ± 0.36° F (± 0.20° C)
Temperature Limits –4° to 221° F (–20° to 105° C)
Wiring 22 AWG wire leads
Case Black plastic standard; metal optional
Maintenance
No routine maintenance is required. Each component is designed for dependable, long-term reliability and performance. Careful installation will also ensure long-term reliability and performance.